Power Quality of Single-Phase and Three-Phase 10 kVA STC Alternators in a Solar–Battery–Motor–Flywheel System
ZONGO Lamoussa Bernard *
Laboratory of Renewable Thermal Energy (LETRE), Joseph KI-ZERBO University, Ouagadougou, Burkina Faso.
YE Siédouba Georges
Laboratory of Renewable Thermal Energy (LETRE), Joseph KI-ZERBO University, Ouagadougou, Burkina Faso and Laboratory of Renewable Energy Systems and Environment–Mechanical and Industrial Engineering (LASERE-GMI), Institute for Research in Applied Sciences and Technologies, National Center for Scientific and Technological Research (CNRST), Ouagadougou, Burkina Faso.
KAM Sié
Laboratory of Renewable Thermal Energy (LETRE), Joseph KI-ZERBO University, Ouagadougou, Burkina Faso.
*Author to whom correspondence should be addressed.
Abstract
Power quality is an important consideration in solar–battery–motor–flywheel systems, as variations in alternator terminal voltage and waveform distortion may affect electrical performance. Evaluating the voltage characteristics of single-phase and three-phase alternators under different operating conditions is essential for understanding their power-quality behaviour and suitability for practical applications. This study characterises the output-voltage quality of two 10 kVA STC-type synchronous alternators operated separately in a photovoltaic–battery–electric-motor–flywheel arrangement. A 34 kg flywheel and a 2.2 kW drive motor were incorporated into the test assembly. Voltage waveforms, rotational speeds and selected electrical powers were documented using an oscilloscope, a tachometer and electrical meters. During 12 observations at five-minute intervals, the single-phase alternator delivered a mean no-load voltage of 239.50 V at recorded mean flywheel and alternator speeds of 1,485.58 and 1,526.08 rpm, respectively. The single-phase waveform was visibly distorted relative to the observed utility waveform. Using the reported harmonic amplitudes of 35, 28 and 18 V and an assumed RMS convention, the corresponding three-component voltage THD estimate is 20.59%. For the three-phase test, the 12 operating observations gave mean phase and line voltages of 476.92 and 786.85 V, with a recorded mean rotational speed of 2,672.25 rpm. During a separate 3 kW load trial, the reported phase and line voltages were 236 and 410 V. The observations identify output-voltage distortion and substantial differences between unloaded and loaded voltages. They also motivate improved excitation regulation, load-specific power-quality assessment and synchronised electrical–mechanical monitoring for this class of generator arrangement.
Keywords: Alternator, flywheel energy storage, harmonic distortion, power quality, synchronous generator, voltage regulation